NLR HPC Facility Power Usage Effectiveness (PUE) Data
Timeseries of Energy Systems Integration Facility (ESIF) Data Center Power Usage Effectiveness (PUE) Data provided in Parquet and compressed CSV formatsPower Metrics Timeseries Fields:ts: Timestampcooling_kw: Cooling (kilowatts) - Captures the power used by fans and pipe trace heaters associated with outdoor cooling equipment. The dedicated tower filter pump power is also captured as cooling load.energy_reuse: Energy Reuse Effectivenesshvac_kw: Heating, ventilation, and air conditioning (kilowatts) - Captures fan walls, fan coils that support the data center electrical rooms, and the make-up air unit.it_power_kw: IT equipment (kilowatts) - Captures power used by the IT equipment on the data center floor.plug_and_light_kw: Lights and utility plugs (kilowatts) - Captures power associated with the data center and dedicated mechanical room. The crank-case heater for the emergency standby generator is also captured as light and plug load.pue: Power Usage Effectivenesspump_kw: Pumps (kilowatts) - Captures power from pumps that move water in the data center Energy Recover Water loop and the Tower Water loops, and also captures power used by the boost pumps that circulate water through the fan walls. Note: The tower filter pump runs constantly to filter water from the data center cooling tower system, so 2.67 kilowatts are attributed to this pump and that is not reflected in this data field.day: Day of monthOutside Weather Station Timeseries Fields:ts: Timestampoutside_air_humidity: Outside air humidity - Relative humidity percentoutside_air_temp: Outside air temperature - Degrees Fahrenheitday: Day of monthMore detail: High-Performance Computing Data Center Power Usage Effectiveness
Complete Metadata
| @type | dcat:Dataset |
|---|---|
| accessLevel | public |
| bureauCode |
[
"019:20"
]
|
| contactPoint |
{
"fn": "Struan Clark",
"@type": "vcard:Contact",
"hasEmail": "mailto:Struan.Clark@nlr.gov"
}
|
| dataQuality |
true
|
| description | Timeseries of Energy Systems Integration Facility (ESIF) Data Center Power Usage Effectiveness (PUE) Data provided in Parquet and compressed CSV formatsPower Metrics Timeseries Fields:ts: Timestampcooling_kw: Cooling (kilowatts) - Captures the power used by fans and pipe trace heaters associated with outdoor cooling equipment. The dedicated tower filter pump power is also captured as cooling load.energy_reuse: Energy Reuse Effectivenesshvac_kw: Heating, ventilation, and air conditioning (kilowatts) - Captures fan walls, fan coils that support the data center electrical rooms, and the make-up air unit.it_power_kw: IT equipment (kilowatts) - Captures power used by the IT equipment on the data center floor.plug_and_light_kw: Lights and utility plugs (kilowatts) - Captures power associated with the data center and dedicated mechanical room. The crank-case heater for the emergency standby generator is also captured as light and plug load.pue: Power Usage Effectivenesspump_kw: Pumps (kilowatts) - Captures power from pumps that move water in the data center Energy Recover Water loop and the Tower Water loops, and also captures power used by the boost pumps that circulate water through the fan walls. Note: The tower filter pump runs constantly to filter water from the data center cooling tower system, so 2.67 kilowatts are attributed to this pump and that is not reflected in this data field.day: Day of monthOutside Weather Station Timeseries Fields:ts: Timestampoutside_air_humidity: Outside air humidity - Relative humidity percentoutside_air_temp: Outside air temperature - Degrees Fahrenheitday: Day of monthMore detail: High-Performance Computing Data Center Power Usage Effectiveness |
| distribution |
[
{
"@type": "dcat:Distribution",
"title": "Timeseries of ESIF DC Power Metrics (Parquet format)",
"accessURL": "https://data.nrel.gov/system/files/300/1757103411-esif.influx.buildingData.PUE.combined.parquet",
"mediaType": "application/octet-stream",
"description": "Timeseries of ESIF DC Power Metrics (Parquet format)"
},
{
"@type": "dcat:Distribution",
"title": "Timeseries of ESIF DC Power Metrics (Zipped CSV format)",
"accessURL": "https://data.nrel.gov/system/files/300/1757105566-esif.influx.buildingData.PUE.combined.csv.zip",
"mediaType": "application/octet-stream",
"description": "Timeseries of ESIF DC Power Metrics (Zipped CSV format)"
},
{
"@type": "dcat:Distribution",
"title": "Timeseries of ESIF DC Outside Weather Station (Zipped CSV format)",
"accessURL": "https://data.nrel.gov/system/files/300/1757105566-esif.influx.buildingData.outside.combined.csv.zip",
"mediaType": "application/octet-stream",
"description": "Timeseries of ESIF DC Outside Weather Station (Zipped CSV format)"
},
{
"@type": "dcat:Distribution",
"title": "Timeseries of ESIF DC Outside Weather Station (Parquet format)",
"accessURL": "https://data.nrel.gov/system/files/300/1757105566-esif.influx.buildingData.outside.combined_2.parquet",
"mediaType": "application/octet-stream",
"description": "Timeseries of ESIF DC Outside Weather Station (Parquet format)"
},
{
"@type": "dcat:Distribution",
"title": "Dataset description",
"accessURL": "https://data.nrel.gov/system/files/300/1769711385-README.md",
"mediaType": "application/octet-stream",
"description": "Dataset description"
}
]
|
| identifier | https://data.openei.org/submissions/8616 |
| issued | 2026-01-29T18:38:14Z |
| keyword |
[
"ESIF",
"HPC",
"PUE",
"power"
]
|
| landingPage | https://data.nrel.gov/submissions/300 |
| license | https://creativecommons.org/licenses/by/4.0/ |
| modified | 2026-01-29T18:42:54Z |
| programCode |
[
"019:000",
"019:023"
]
|
| projectNumber | DE-AC36-08GO28308 |
| projectTitle | |
| publisher |
{
"name": "National Laboratory of the Rockies",
"@type": "org:Organization"
}
|
| title | NLR HPC Facility Power Usage Effectiveness (PUE) Data |