Data from Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner
These data from the laboratory tests of a prototype residential liquid-to-air ground-source air conditioner (GSAC) using CO2 as the refrigerant. The data collection and processing methods are described in detail in this report:
Report Title: "Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner", NIST Technical Note 2068
Publication Date: October 2019
DOI: https://doi.org/10.6028/NIST.TN.2068
Authors: Harrison Skye, Wei Wu
The tests were performed in an environmental chamber and followed the ISO 13256-1 standard for rating GSHPs. The CO2 GSAC operated either in a subcritical or a transcritical cycle, depending on the entering liquid temperature (ELT). The test results included the coefficient of performance (COP), capacity, sensible heat ratio (SHR), and pressures. The system incorporated a liquid-line/suction-line heat exchanger (LLSL-HX), which was estimated to cause a COP penalty of (0 to 2) % for ELTs ranging (10 to 25) °C, and benefit of (0 to 5) % for ELTs ranging (30 to 39) °C. With ELTs ranging (10 to 39) °C the CO2 system cooling COP ranged (7.3 to 2.4). At the standard rating condition (ELT 25 °C), the CO2 GSAC cooling COP was 4.14, and at part-load conditions (ELT 20 °C) the system had a COP of 4.92.
Complete Metadata
| @type | dcat:Dataset |
|---|---|
| accessLevel | public |
| bureauCode |
[
"006:55"
]
|
| contactPoint |
{
"fn": "Harrison M. Skye",
"hasEmail": "mailto:harrison.skye@nist.gov"
}
|
| description | These data from the laboratory tests of a prototype residential liquid-to-air ground-source air conditioner (GSAC) using CO2 as the refrigerant. The data collection and processing methods are described in detail in this report: Report Title: "Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner", NIST Technical Note 2068 Publication Date: October 2019 DOI: https://doi.org/10.6028/NIST.TN.2068 Authors: Harrison Skye, Wei Wu The tests were performed in an environmental chamber and followed the ISO 13256-1 standard for rating GSHPs. The CO2 GSAC operated either in a subcritical or a transcritical cycle, depending on the entering liquid temperature (ELT). The test results included the coefficient of performance (COP), capacity, sensible heat ratio (SHR), and pressures. The system incorporated a liquid-line/suction-line heat exchanger (LLSL-HX), which was estimated to cause a COP penalty of (0 to 2) % for ELTs ranging (10 to 25) °C, and benefit of (0 to 5) % for ELTs ranging (30 to 39) °C. With ELTs ranging (10 to 39) °C the CO2 system cooling COP ranged (7.3 to 2.4). At the standard rating condition (ELT 25 °C), the CO2 GSAC cooling COP was 4.14, and at part-load conditions (ELT 20 °C) the system had a COP of 4.92. |
| distribution |
[
{
"title": "DOI Access for Data from Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner",
"accessURL": "https://doi.org/10.18434/M32142"
},
{
"title": "Readme",
"format": ".txt",
"mediaType": "text/plain",
"description": "Description of the dataset",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/README.txt"
},
{
"title": "Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner, NIST Technical Note 2068",
"format": "Comma Separated Values (CSV)",
"mediaType": "application/vnd.ms-excel",
"description": "This data is from the appendix of the publication. The data are for the system at steady state, and are an average of 120 samples taken over 30 minutes.",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/CO2_GSAC_Lab_Tests%20%28TN%202068%29%20-%20Appendix%20data.csv"
},
{
"title": "Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner, NIST Technical Note 2068",
"format": "Microsoft Excel (*.xlsx)",
"mediaType": "application/vnd.openxmlformats-officedocument.spreadsheetml.sheet",
"description": "This data is from the appendix of the publication. The data are for the system at steady state, and are an average of 120 samples taken over 30 minutes.",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/CO2_GSAC_Lab_Tests%20%28TN%202068%29%20-%20Appendix%20data.xlsx"
},
{
"title": "SHA256 File for Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner, NIST Technical Note 2068",
"mediaType": "text/plain",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/CO2_GSAC_Lab_Tests%20%28TN%202068%29%20-%20Appendix%20data.csv.sha256"
},
{
"title": "SHA256 File for Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner, NIST Technical Note 2068",
"mediaType": "text/plain",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/CO2_GSAC_Lab_Tests%20%28TN%202068%29%20-%20Appendix%20data.xlsx.sha256"
},
{
"title": "SHA256 File for Readme",
"mediaType": "text/plain",
"downloadURL": "https://data.nist.gov/od/ds/mds2-2142/README.txt.sha256"
}
]
|
| identifier | ark:/88434/mds2-2142 |
| issued | 2020-01-13 |
| keyword |
[
"Air conditioner",
"CO2",
"carbon dioxide",
"ground-source heat pump",
"subcritical and transcritical cycles"
]
|
| landingPage | https://data.nist.gov/od/id/mds2-2142 |
| language |
[
"en"
]
|
| license | https://www.nist.gov/open/license |
| modified | 2019-10-11 00:00:00 |
| programCode |
[
"006:045"
]
|
| publisher |
{
"name": "National Institute of Standards and Technology",
"@type": "org:Organization"
}
|
| references |
[
"https://doi.org/10.6028/NIST.TN.2068"
]
|
| theme |
[
"Energy:Energy efficiency"
]
|
| title | Data from Laboratory Tests of a Prototype Carbon Dioxide Ground-Source Air Conditioner |